TIANJIN ESTEL ELECTRONIC SCIENCE AND TECHNOLOGY CO., LTD

 

We are the professoinal supplier of outdoor telecom cabinet, air conditioner, heat exchanger, and telecom power system.

Sales & Support
Request A Quote - Email
Select Language
English
Portuguese
中文
Home
Products
About Us
Factory Tour
Quality Control
Contact Us
Request A Quote
Home ProductsTelecom Power System

GPE4890A & GPE4890B, Telecom Power System/UPS/Rectifier,Input:90~280;Output:-42~-58Vac

Certification
Good quality Two Compartments Outdoor Telecom Cabinet for sales
Good quality Two Compartments Outdoor Telecom Cabinet for sales
Timely response, professional skills, rigorous attitude, fast delivery, we are very satisfied, cooperation is very smooth.

—— Manish

From 1 sample to 45 sets, 76 sets, 200sets, we gradually established a strong trust. The cabinet quality is good and the design is reasonable.

—— Parmar

In the past three years, our cooperation is very cheerful, thanks for your company's technical support and patient service, the end user is very satisfied with the quality of outdoor telecom cabinet with cooling. Best wishes to our future cooperation.

—— Anthony

The air conditioner have been running for one and a half years. Cooling effective is good. Good after-sale service, and patiently instruct to use and solve technical problems. Environmental monitoring system is also running well, and remote monitoring the cabinet is very convenient.

—— Luis Alberto

I'm Online Chat Now

GPE4890A & GPE4890B, Telecom Power System/UPS/Rectifier,Input:90~280;Output:-42~-58Vac

China GPE4890A & GPE4890B, Telecom Power System/UPS/Rectifier,Input:90~280;Output:-42~-58Vac supplier
GPE4890A & GPE4890B, Telecom Power System/UPS/Rectifier,Input:90~280;Output:-42~-58Vac supplier GPE4890A & GPE4890B, Telecom Power System/UPS/Rectifier,Input:90~280;Output:-42~-58Vac supplier

Large Image :  GPE4890A & GPE4890B, Telecom Power System/UPS/Rectifier,Input:90~280;Output:-42~-58Vac

Product Details:

Place of Origin: China
Brand Name: ESTEL
Certification: ISO9001:2008
Model Number: GPE4890A & GPE4890B

Payment & Shipping Terms:

Minimum Order Quantity: 1 Set
Packaging Details: Wooden Case
Delivery Time: 15 days
Payment Terms: T/T, L/C
Supply Ability: 15000 Sets Per Year
Contact Now
Detailed Product Description

Power System of High Performance and High Reliability

GPE4890A & GPE4890B Embedded Power System

Input:90~280Vac; Output: -42~-58Vdc;

Main features
 
Adoption of active power factor compensation technology with factor >0.98
Wide operating range of AC input voltage: 90~280Vac
Operating temperature range:-25°C~+55°C
Zero current/voltage switching tech with high efficiency ≥90%
Perfect battery management, charge&discharge management, battery temperature compensation, low voltage protection, battery capacity test
Hot-swappable
Input over/under voltage protection
Output over voltage protection
Output over current protection
Output short circuit protection
Auto current sharing, parallel operation
Embedded mounted
 
Application
 
■   Small scale program controlled exchanger
■   Access network
■   Transmission equipment
■   Mobile communication
■   Satellite communication ground station
■   Microwave communication
 
GPE4890A & GPE4890B consist of the power distribution frame, monitoring module and rectifier module. The whole system is of high reliability and performance, and can be operated through PC software.
 
1. General
 
1.1 GPE4890A&GPE4890B System Configuration
 
GPE4890A&GPE4890B consists of distribution unit, rectifier module (up to 3 sets) and 1 monitoring module. The configuration is optional, as following table: 
 

Configuration

Rectifier Module

Monitoring Module

Power Distribution

Remark

Standard

GPR4830A1 

GPM48DI (With Ethernet Port)

GPE4890A:

AC Input: 40A×1;

DC Output: 40A×4 (load);

Battery Output: 70A×1 (battery)

For details, please refer to the 

specifications of modules.

Optional 1

GPR4830A

GPM48D  (Without Ethernet Port)

GPE4890B:

DC Output: 40A×4 (load);

Battery Output: 70A×1 (battery)

Optional 2

GPR4810A

Optional 3

GPR4815A

Optional 4

GPR4820A

 
 
1.2 GPE4890A&GPE4890B Operating Principle
 
Under normal conditions, every parameter of rectifier modules and distribution unit are all under control of the monitoring module, operating according to the pre-set parameter or user’s commands. If AC mains fault, the system will be powered by the battery. With the battery discharge, the terminal voltage of the battery starts to descend. When the battery voltage is under 42V±0.5V, the monitoring module reports battery under voltage alarm signal and cuts off the load output, then the power system stops working. When the external AC mains recovers, the system will resume to the normal work state. (All above monitoring data are system default values that users can reset).
 
 
1.3 GPE4890A&GPE4890B System Properties
 

Input

Parameter

Min.

Typical

Max.

Unit

Remark

Input voltage range

90

220

280

Vac

 

Input frequency

45

50

65

Hz

 

Input current

 

 

29.7

A

                                   

Power factor

0.98

 

 

 

 

 

Output

Parameter

Min.

Typical 

Max.

Unit

Remark

Output voltage range

-42

-53.5

-58

Vdc

 

Output current range

0

 

90

A

176~280VAC

0

 

45

A

90~175VAC

Ripple (Vp-p)

 

 

200

mv

At rated input/output, apply 0.1uF film capacitor and 10uF HF electrolyte capacitor, oscilloscope band width of 20MHz.

Output efficiency

90

92

 

%

220Vac input

83

85

 

%

110Vac input

Regulation

 

 

±1

%

 

Load regulation

 

 

±1

%

 

Line regulation

 

 

±1

%

 

 

Insulation rating

Parameter

Min

Remark

Input - output

2121Vdc/10mA//1min

 

Input-chassis

2121Vdc/10mA//1min

 

Output - chassis

750Vdc/10mA//1min

 

Insulation resistance

At normal atmospheric pressure, relative humidity: 90%,testing voltage: 500vdc,insulation of input-output, input-ground, output-ground shall not be less than 10MΩ

 

Ambient requirements

Parameters

Min.

Typical

Max.

Unit

Remark

Operating temp

-25

 

+55

°C

≥ 55°C, output with derating power

Storage tempStorage temperature

-40

 

+80

°C

 

Humidity

10

 

90

%

Relative humidity, no condensing

Atmospheric pressure

70

 

106

KPa

 

Altitude

0

 

3000

m

 

Cooling method

Forced cooling with fan

 

Mechanical specifications

Dimensions (Overall)

482.6mm×255mm×86.1mm

Weight(kg) (Overall)

≤11kg (Inclusive of module)

≤5.175kg (Frame + Distribution, exclusive of module)

GPE4890A & GPE4890B, Telecom Power System/UPS/Rectifier,Input:90~280;Output:-42~-58Vac

2. Installation
 
2.1 Dimensions Diagram
 
GPE4890A & GPE4890B, Telecom Power System/UPS/Rectifier,Input:90~280;Output:-42~-58Vac
2.2 GPE4890A&GPE4890B Installation
 
GPE4890A&GPE4890B is embedded power system. First insert GPE4890A&GPE4890B to the specified location till the system is well fixed. Keep the 4 fixing holes on the bracket in line with those on the cabinet and then screw up 4 M4 cross rounded head screws, with the spring washer and flat washer. At last finish the installation after tightening the screw.
 
3. Electric Connection
 
3.1 Electric Connection Instruction 
 
Chassis connects with external electric through system interface board. As shown in figure below: 
 
GPE4890A & GPE4890B, Telecom Power System/UPS/Rectifier,Input:90~280;Output:-42~-58Vac
Connector Instruction:
(1) L,N,PE is power supply three-core AC input port;
(2) LOAD(+) is load positive, LOAD(-) is load negative;
(3) BAT(+), BAT(-) are battery port
 
3.2 Process of Electric Connection
 
Electric connection between main cabinet and external component includes: connection of AC input line, connection of DC output and battery, connection of communication cables, connection of GND cables. The main requirements of electrical connection are safety and reliability. The followings are detailed description.
 
(1) AC input cable connections
The connectors for AC input cable are three-core AC input sockets on the front panel of system. The AC cable can be directly inserted to the connector.
 
(2) Connection of DC load cables
The terminals for load connection of the system are LOAD1, LOAD2, LOAD3, LOAD4, totally four 2PIN, locating on the front panel of the system. The cable can be directly inserted into the terminal. 
a. The specifications and model of the load cables shall be according to the engineering design requirements.
b. Connect one end of anode cable to “LOAD+” on the front panel of the system;
c. Connect one end of cathode cable to “LOAD-” on the front panel of the system;
 
(3) Connection of DC battery cables
The power system terminals for battery connection is 2PIN connector, signed as BAT+ and BAT-. The cable can be directly inserted to the terminal. The detailed process of battery connection is as following: 
a. Prepare positive connection cables and negative connection cables(including terminals and polarity identifications ready).
b. Fasten up the battery connection cable
c. Connect one end of positive connection cable to the BAT. “+” on the front panel of the system;
d. Connect one end of negative connection cable to the BAT. “-” on the front panel of the system;
 
(4)Recommended Cable Specifications
 

Item

   Sign

AWG/ Min. Section

(#/mm2)

AWG / Max. Section

(#/mm2)

Temp Rating

(°C)

Withstand Voltage

(V)

Output anode wire

Lout1, Lout2,

Lout1 Lout1

12#/4

10#/5.5

105

600

Output GND wire

GND

12#/4

10#/5.5

105

600

Input GND wire

PEin

9#/6

6#/10

105

600

Mains neutral wire

Nin

10#/5.5

6#/10

105

600

Mains live wire

Lin

10#/5.5

6#/10

105

600

Battery +

(BATTERY+)

7#/8

6#/10

105

600

Battery -

(BATTERY -)

7#/8

6#/10

105

600

 
(5) Connection of GND Cables
PE connection: Connect the chassis GND point of system main cabinet and external earth with cable of 12mm2 above.
(6)Connection of Communication Cables
Communication interface RS485 of GPE4890B locate at the front panel of the system. RS485 is commnication port, with function of communication with the host. 
RS485 communication mode:
a. Connect one end of communication cable to RS485 at front panel of GPE4890B.
b. Connect the other end of communication cable to RS485 on host. RS485 anode, cathode line of GPE4890B respectively corresponding with RS485 anode, cathode line of host.
 
4. GPM48DI Monitoring Module
 
4.1 Functions of Monitoring Module

Item

Remark

Remote monitoring of the host

The host can conduct enquiries, settings and control upon the monitoring and realize the remote message, remote sense and remote control.

Rectifier management by monitoring module

To send controlling orders or to get data from the rectifier module via 

RS485 communication.

Battery management

To manage low voltage, power down, equalizing/float charge,

 temperature compensation of the battery.  

Output management by monitoring module

To inspect and control the system

LED indicator

Signal indication

6 way dry contact output 

Dry contact setting

COM port signal definition

 

LCD Display

Set and revise menu 

For details, please refer to specifications of “GPM48DI”.

 
 
4.2 Installation of monitoring module
 
Handles on panel of monitoring module are equipped. When inserting module into the main cabinet, the operator shall clutch the handle with one hand while holding it with the other hand. Slowly push the module into its slot until the connection terminal on back of the module inserted into corresponding socket of system bar in the main cabinet. Finally, finish the installation by firmly fixing the screw on the panel to the main cabinet. 
 
When removing module from the main cabinet, first screw off the bolt on panel then slowly remove the module from its slot while clutching the handle. 
 
5. GPR4830A1 Rectifier Module
 
5.1 Properties
 

Item

Unit

Min.

Typical

Max.

Remarks

AC input voltage

Vac

90

220

280

 

AC input voltage frequency

Hz

45

50

65

Rated load

Input power factor

 

0.98

 

 

Rated voltage/ rated load

Output voltage range

Vdc

-42

-54

-58

 

Output current

A

0

30

 

176~290V ac Input 

Output voltage regulation

 

 

 

±1%

 

Ripple (Vp-p)

mV

 

 

200

With 0.1uF filmy capacitor and 10uF high frequency 

electrolyte capacitor, oscilloscope band width of 20MHz.

Output power

W

0

1600

 

176-280V Input

W

0

800

 

90-175V Input

Output efficiency

%

91

 

 

220V AC Input

%

83

 

 

110V AC Input

Input over-voltage protection

Vac

285

305

 

Tested with 15A, auto recoverable

Input over-voltage recovery set point

Vac

280

 

 

Hysteresis not less than 5V.

Input under-voltage protection

Vac

 

 

85

Tested with 4A, auto recoverable

Input under-voltage recovery set point

Vac

 

 

90

Hysteresis not less than 5V.

Output over-voltage protection set point

V

-58.5

-59

-61.5

Lock up

Output current limiting

A

32

33

34

Auto recoverable

Short circuit protection

A

Long-term short circuit endurable; Hiccup when short circuit detected; Auto recoverable

Thermal protection

 

Auto recoverable under ambient temperature of 65°C.

For details, please refer to specifications of “GPR4830A1”.

 
5.2 Installation of Rectifier Module
 
Handles on panel of rectifier module are equipped. When inserting module into the main cabinet, the operator shall clutch the handle with one hand while holding it with the other hand. Slowly push the module into its slot until the connection terminal on back of the module inserted into corresponding socket of system bar in the main cabinet. Finally, finish the installation by firmly fixing the screw on the panel to the main cabinet. 
 
When removing module from the main cabinet, first screw off the bolt on panel then slowly remove the module from its slot while clutching the handle. 
 
6. System Maintenance
 
(1) Failure: yellow LED on rectifier module flickers, communication fails;
Maintenance solution: check the communication network to see whether the internet connection is loose, internet interface is damaged, or network wire is damaged.
(2) Failure: yellow LED on rectifier lights on;
Maintenance solution: check whether the fan is blocked, load current exceeds the max. value; AC voltage is too low, then the auto rate decrease starts; over temperature pre-alarm starts; remote shut-down is started on PC software.
(3) Failure: Red LED on rectifier lights on;
Maintenance solution: check whether the voltage is too high/too low and over/under voltage protection is on; fan is blocked; ambient temperature is too high; load is short circuit or not.
If above mentioned parts are ok but the red LED is still on, then there is problem on the module, please return it to factory for repairing.
(4) Failure: Yellow, red, green LEDs on rectifier are all off;
Maintenance solution: firstly check whether AC input is available or not, if not, then check the electrical circuit; if yes, the module is in malfunction, please return the module to factory for repairing.
 

 